Overview

The Hioki DT4200 Digital Multimeter Series consist of a complete lineup of 9 models ranging from professional to industrial to pocket meters, delivering a super fast response rate and safety features that take electrical testing to a higher level. The DT4256 is a digital multimeter designed to deliver maximum functionality for use in a wide range of settings.

CAT IV 600 V, CAT III 1000 V

Key Features

  • ?0.3% DC V basic accuracy, wide 40 Hz to 1 kHz AC V frequency characteristics
  • Measure up to 10A with direct input
    ? Dual display lets you check voltage and frequency simultaneously
  • Low-pass filter cuts high harmonics (when measuring inverter fundamental waveforms)
  • USB communications function supports PC measurements (optional)
  • Broad -25 (-13?F) to 65?C (149?F) operating temperature range (DT4256)

Technical Specifications

  Basic specifications (Accuracy guaranteed for 1 year, Post-adjustment accuracy guaranteed for 1 year)
DC Voltage 600.0 mV to 1500 V, 5 ranges, Basic accuracy: ?0.3 % rdg. ?3 dgt.
AC Voltage 6.000 V to 1000 V, 4 ranges, Frequency characteristics 40 Hz to 1 kHz, Basic accuracy 40 – 500 Hz : ?0.9 % rdg. ?3 dgt. (True RMS, crest factor 3)
AUTO AC/DCV Yes
Resistance N/A
DC Current N/A
From 4 to 20mA Percentage conversion display N/A
AC Current (use with Clamp on probes) N/A
Temperature (thermocouples) N/A
Voltage detection Hi: AC40 V to 600 V, Lo: AC80 V to 600 V
C (capacitance) N/A
Frequency 99.99 Hz to 99.99 kHz, 4 ranges (limited by the minimum detectable voltage), Basic accuracy: ?0.1 % rdg. ?1 dgt.
Continuity check N/A
Diode test N/A
Other functions Filter function, Display value hold, Auto hold, Max/Min/Average value display, Relative display, Auto-power save, USB communication (option)
Display Main and Sub displays: 4-digits LCD, max. 6000 digits, bar graph
Display refresh rates 5 times/s (Capacitance measurement: 0.05 to 5 times/s, depending on measured value, Frequency: 1 to 2 time/s)
Power supply LR03 alkaline batteries _4, Continuous use: 130 hours (backlight OFF)
Dimensions and mass 84 mm (3.31 in)W _ 174 mm (6.85 in)H_ 52 mm (2.05 in)D, 390 g (13.8 oz) (including batteries and holster)
Accessories Test lead L9207-10 _1, Holster _1, Instruction manual _1, LR03 alkaline battery _4

Others

N/A