Basic specifications (Accuracy guaranteed for 1 year, Post-adjustment accuracy guaranteed for 1 year) |
Measurement line type |
Single-phase 2-wire, Single-phase 3-wire, Three-phase 3-wire or Three-phase 4-wire plus one extra input channel CH4 for voltage/current, (all channels AC/DC measurement) |
Voltage ranges |
Voltage measurement: 1000.0 V rms or DC, Transient measurement 2.200 kV peak |
Current ranges |
50.000 mA AC to 5.0000 kA AC, 10.000 A DC to 2.0000 kA DC(depends on current sensor in use) |
Power ranges |
50.000 W to 6.0000 MW (determined automatically based on current range in use) |
Basic accuracy |
Voltage: ?0.2% of nominal voltage, Current: ?0.1 % rdg. ?0.1 % f.s. + current sensor accuracy, Active power: DC ?0.5 % rdg. ?0.5 % f.s. + current sensor accuracy, AC ?0.2 % rdg. ?0.1 % f.s. + current sensor accuracy |
Measurement items |
1. Transient over voltage : 200 kHz sampling; 2. Frequency cycle : Calculated as one cycle; 3. Voltage (1/2) RMS, Current (1/2) RMS: one cycle calculation refreshed every half cycle; 4. Voltage swell, Voltage dips, Voltage interruption, RVC (Ver. up) : Voltage (1/2) RMS calculation; 5. Inrush current : half-cycle calculation: Calculated as the current RMS value for current waveform data sampled every half-cycle.; 6. Frequency 200 ms: Calculated as 10 or 12 cycles; 7. 10-sec frequency: Calculated as the whole-cycle time during the specified 10 s period; 8. Voltage waveform peak, Current waveform peak; 9. Voltage, Current, Active power, Apparent power, Reactive power, Active energy, Apparent energy, Reactive energy, Energy cost, Power factor, Displacement power factor, Voltage unbalance factor, Current unbalance factor; 10. Voltage crest factor, Current crest factor; 11. Harmonic/ Harmonic phase angle (voltage/ current), Harmonic power: 0 th to 50 th orders; 12. Harmonic voltage-current phase angle: 1 th to 50 th orders; 13. Total harmonic distortion factor (voltage/ current); 14. Inter harmonic (voltage/ current): 0.5 th to 49.5 th orders; 15. K Factor (multiplication factor); 16. IEC Flicker, _ V10 Flicker |
Record |
Maximum recording interval: 1 year, Maximum number of recordable events: 9999 _ 365 days |
Interfaces |
SD/SDHC memory card, RS-232C (for communication/ LR8410 link), LAN (HTTP server/ FTP/ Send e-mail), USB 2.0 (for communication) |
Logger connectivity |
Sends measured values wirelessly to logger by using a Bluetooth_ wireless technology serial conversion adapter. (Supported devices: Hioki LR8410 Link-compatible loggers), Ver. 2.0 and later |
Display |
6.5-inch TFT color LCD (640 _ 480 dots) |
Power supply |
AC adapter Z1002 (100 V to 240 V AC, 50/60 Hz, rated current 1.7 A), Battery pack Z1003 (Continuous use: 8 hr, Charging time: Max. 5 hr 30 m with AC adapter) |
Dimensions and mass |
300 mm (11.81 in)W _ 211 mm (8.31 in)H _ 68 mm (2.68 in)D, 2.5 kg (88.2 oz) (including battery pack) |
Accessories |
Instruction manual _1, Measurement guide _1, Voltage cord L1000-05 _1 set (Red/Yellow/Blue/Gray/Black, Alligator clip _5, Spiral tube _5), Color clip (for identifying clamp sensor color) _1 set, Spiral tube _5, AC adapter Z1002 _1, Strap _1, USB cable (1 m 3.28 ft length) _1, Battery pack Z1003 _1, PQ ONE (software, CD) _1 |